High Accuracy
Provides precise flow rate measurements
Durable Design
Rugged stainless steel construction for harsh environments
Easy Integration
Simple installation with plug & play connectivity
Communication
4…20 mA 0…10 V

Flow sensor with integrated microcontroller for measuring air velocity, air temperature, and volumetric flow in m³/h.
The compact sensor head causes no significant additional pressure loss in the duct and is largely insensitive to contamination.

Flow measurement is performed calorimetrically using the heat transfer principle. A heated resistor is controlled to maintain a constant temperature difference relative to the medium temperature. As the mass flow increases, heat transfer to the medium (air) increases accordingly. The required heating voltage is a direct measure of the normalized flow velocity.

TECHNICAL DATA

Vmax 0.0 to 25.0 m/s
Medium Air / Nitrogen
Measurement Accuracy ±3.6% of full-scale value
Signal Output, Volumetric Flow 4–20 mA [m³/h], linearized
Signal Output, Temperature (optional) 4–20 mA [°C], linearized
Operating Temperature Range 0–50 °C
Storage Temperature –10–60 °C
Power Supply 12–24 V DC
Connection M12 connector

APPLICATIONS

Supply and exhaust air monitoring
Volumetric flow control
HVAC systems
Leakage detection
Fan control